Elmwood Leisure Centre · Primary Plant Room Schematic

HEN0203-HEN-00-ZZ-DR-M-5991 rev AF01 · As fitted record · O&M manual Vol 6 p126

ASHP 0.01 primary return riser (38°C) From ASHP return header to ASHP 0.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mASHP 0.01 primary flow riser (45°C) From ASHP 0.01 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mASHP 0.01 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP 0.01 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP 0.02 primary return riser (38°C) From ASHP return header to ASHP 0.02 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mASHP 0.02 primary flow riser (45°C) From ASHP 0.02 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mASHP 0.02 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP 0.02 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP 0.03 primary return riser (38°C) From ASHP return header to ASHP 0.03 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 2.5 kg/s, 63mm, 1.24 m/s, 276 Pa/mASHP 0.03 primary flow riser (45°C) From ASHP 0.03 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 2.5 kg/s, 63mm, 1.24 m/s, 276 Pa/mASHP 0.03 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP 0.03 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP flow header, ASHP 0.01 section From ASHP 0.01 to Header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mASHP flow header, external MDPE From ASHP 0.01 and 0.02 to Header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 26.4 kg/s, 180mm, 1.59 m/s, 123 Pa/mASHP flow header, external preinsulated MDPE main From All ASHPs to Plant room Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 180mm, 1.74 m/s, 146 Pa/mASHP primary flow into the thermal store (internal steel) From ASHP flow header to TS B.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 150mm, 1.56 m/s, 128 Pa/mASHP primary return from the thermal store (internal steel) From TS B.01 to ASHP return header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 150mm, 1.56 m/s, 128 Pa/mASHP return header, external MDPE Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 180mm, 1.74 m/s, 146 Pa/mASHP return header, external MDPE Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 26.4 kg/s, 180mm, 1.59 m/s, 123 Pa/mASHP return header, ASHP 0.01 section Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/mPrimary flow from the thermal store to the dirt separator (45°C) From TS B.01 to Dirt/air separator Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/mPrimary flow to the low loss header (45°C) From Dirt/air separator to Low loss header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/mDosing pot connection from the primary flow Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Dosing pot connection to the primary return Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Capped off connection on the low loss header (flow side) Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Capped off connection on the low loss header (return side) Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)ASHP primary return, low loss header to thermal store (38°C) From Low loss header to TS B.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/mPressurisation unit pump suction from the tank Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Pressurisation unit pump 1 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Pressurisation unit pump 2 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Pressurisation unit discharge to the low loss header From PU 0.01 to Low loss header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)Tank cold water service to the pressurisation unit tank and quick fill loop Boosted / mains cold water pipework (TCWS)Tank cold water feed to the pressurisation unit tank float valve Boosted / mains cold water pipework (TCWS)AHU constant temperature flow, P B.02 to the AHU riser From Low loss header to AHU flow riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 18.261 kg/s, 150mm, 0.99 m/s, 51.5 Pa/mAHU flow riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 17.810 kg/s, 150mm, 0.95 m/s, 48 Pa/mAHU flow riser to the roof header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/mAHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/mAHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 17.810 kg/s, 150mm, 0.95 m/s, 48 Pa/mAHU constant temperature return to the low loss header From AHU return riser to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 18.261 kg/s, 150mm, 0.99 m/s, 51.5 Pa/mAHU R.02 coil flow From AHU flow header to AHU R.02 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.109 kg/s, 50mm, 0.96 m/s, 191 Pa/mAHU R.02 coil return From AHU R.02 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.109 kg/s, 50mm, 0.96 m/s, 191 Pa/mAHU R.02 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/mAHU R.08 coil flow From AHU flow header to AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.670 kg/s, 32mm, 0.71 m/s, 152 Pa/mAHU R.08 coil return From AHU R.08 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.670 kg/s, 32mm, 0.71 m/s, 152 Pa/mAHU R.08 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.870 kg/s, 100mm, 1.73 m/s, 285 Pa/mAHU return header from AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.870 kg/s, 100mm, 1.73 m/s, 285 Pa/mAHU R.07 coil flow From AHU flow header to AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.416 kg/s, 65mm, 1.47 m/s, 311 Pa/mAHU R.07 coil return From AHU R.07 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.416 kg/s, 65mm, 1.47 m/s, 311 Pa/mAHU R.07 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.200 kg/s, 100mm, 1.65 m/s, 225 Pa/mAHU return header from AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.200 kg/s, 100mm, 1.65 m/s, 225 Pa/mAHU R.01 coil flow From AHU flow header to AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 7.674 kg/s, 80mm, 1.51 m/s, 268 Pa/mAHU R.01 coil return From AHU R.01 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 7.674 kg/s, 80mm, 1.51 m/s, 268 Pa/mAHU R.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 8.784 kg/s, 100mm, 1.06 m/s, 90 Pa/mAHU return header from AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 8.784 kg/s, 100mm, 1.06 m/s, 90 Pa/mAHU R.04 coil flow From AHU flow header to AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.21 kg/s, 20mm, 0.57 m/s, 220 Pa/mAHU R.04 coil return From AHU R.04 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.21 kg/s, 20mm, 0.57 m/s, 220 Pa/mAHU R.04 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.110 kg/s, 40mm, 0.88 m/s, 180 Pa/mAHU return header from AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.110 kg/s, 40mm, 0.88 m/s, 180 Pa/mAHU R.09 coil flow From AHU flow header to AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.530 kg/s, 32mm, 0.61 m/s, 97 Pa/mAHU R.09 coil return From AHU R.09 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.530 kg/s, 32mm, 0.61 m/s, 97 Pa/mAHU R.09 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.900 kg/s, 32mm, 0.96 m/s, 265 Pa/mAHU return header from AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.900 kg/s, 32mm, 0.96 m/s, 265 Pa/mAHU R.05 coil flow From AHU flow header to AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/mAHU R.05 coil return From AHU R.05 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/mAHU R.05 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU R.05 three port valve bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU flow header to AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/mAHU return header from AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/mAHU R.03 coil flow From AHU flow header to AHU R.03 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/mAHU R.03 coil return From AHU R.03 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/mAHU R.03 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)AHU R.06 coil flow From AHU flow header to AHU R.06 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.180 kg/s, 20mm, 0.5 m/s, 163 Pa/mAHU R.06 coil return From AHU R.06 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.180 kg/s, 20mm, 0.5 m/s, 163 Pa/mAHU R.06 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)FOH and spin studio AHU flow Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.830 kg/s, 32mm, 0.91 m/s, 227 Pa/mFOH AHU flow Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/mFOH AHU return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/mFOH and spin studio AHU return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.830 kg/s, 32mm, 0.91 m/s, 227 Pa/mHB 0.01 dry change reheat coil flow From AHU flow riser to HB 0.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.451 kg/s, 25mm, 0.74 m/s, 290 Pa/mHB 0.01 dry change reheat coil return From HB 0.01 to AHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.451 kg/s, 25mm, 0.74 m/s, 290 Pa/mHB 0.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)Pool plate heat exchanger flow, P B.03 From Low loss header to Pool plate heat exchangers Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 6.599 kg/s, 80mm, 1.31 m/s, 201 Pa/mPool plate heat exchanger return to the low loss header From Pool plate heat exchangers to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 6.599 kg/s, 80mm, 1.31 m/s, 201 Pa/m160 kW main pool plate heat exchanger flow From Pool circuit to PHE main pool Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.443 kg/s, 65mm, 1.48 m/s, 314 Pa/m160 kW main pool plate heat exchanger return From PHE main pool to Pool circuit return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.443 kg/s, 65mm, 1.48 m/s, 314 Pa/m160 kW main pool plate heat exchanger flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)160 kW main pool plate heat exchanger three port valve bypass Secondary side LTHW pipework (45/38°C) (SEC)160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)Learner pool plate heat exchanger flow branch Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m40 kW learner pool plate heat exchanger flow From Pool circuit to PHE learner pool Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m40 kW learner pool plate heat exchanger return From PHE learner pool to Pool circuit return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m40 kW learner pool plate heat exchanger flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)Learner pool plate heat exchanger return branch Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/mHot water heater primary flow, P B.04 From Low loss header to HWH B.01 and B.02 coils Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.538 kg/s, 50mm, 1.16 m/s, 271 Pa/mHot water heater primary return to the low loss header From HWH coils to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.538 kg/s, 50mm, 1.16 m/s, 271 Pa/mWH B.01 primary coil flow From Hot water heater primary to WH B.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/mWH B.01 primary coil return From WH B.01 to Hot water heater primary return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/mWH B.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)WH B.01 hot water outlet From WH B.01 to 54mm HWS Domestic hot water pipework (DHW)WH B.01 relief discharge to low level drain Domestic hot water pipework (DHW)WH B.02 primary coil flow From Hot water heater primary to WH B.02 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/mWH B.02 primary coil return From WH B.02 to Hot water heater primary return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/mWH B.02 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)WH B.02 hot water outlet From WH B.02 to 54mm HWS Domestic hot water pipework (DHW)WH B.02 relief discharge to low level drain Domestic hot water pipework (DHW)Cold feed to WH B.01 with expansion vessel and relief valve From Cold feed to WH B.01 Domestic hot water pipework (DHW)Cold feed to WH B.02 with expansion vessel and relief valve From Cold feed to WH B.02 Domestic hot water pipework (DHW)Expansion vessel connection, WH B.01 Domestic hot water pipework (DHW)Expansion vessel connection, WH B.02 Domestic hot water pipework (DHW)Cold feed and secondary return to the hot water heaters From 54mm BCWS / 35mm HWS R to WH B.01 and B.02 Domestic hot water pipework (DHW)Hot water secondary return via P B.05 From 35mm HWS R to Hot water heaters Domestic hot water pipework (DHW)54mm boosted cold water feed to the hot water heaters via PRV From 54mm BCWS to Hot water heaters Boosted / mains cold water pipework (TCWS)Existing tank cold water down service to BS B.01 suction From Existing tank to BS B.01 Boosted / mains cold water pipework (TCWS)BS B.01 pump 1 Boosted / mains cold water pipework (TCWS)BS B.01 pump 2 Boosted / mains cold water pipework (TCWS)BS B.01 pump 3 Boosted / mains cold water pipework (TCWS)Boosted cold water from BS B.01 From BS B.01 to Water conditioner Boosted / mains cold water pipework (TCWS)Relief valve discharge to the discharge point Relief valve discharge (DISCH)BCWS riser (76mm) Boosted / mains cold water pipework (TCWS)BCWS riser Boosted / mains cold water pipework (TCWS)22mm BCWS to serve the heating system pressurisation unit Boosted / mains cold water pipework (TCWS)76mm BCWS to the building Boosted / mains cold water pipework (TCWS)35mm BCWS to the Cat 5 break tank (BS B.02) Boosted / mains cold water pipework (TCWS)Cat 5 break tank outlet to BS B.02 pumps Fluid category 5 boosted water (CAT5B)BS B.02 pump 1 Fluid category 5 boosted water (CAT5B)BS B.02 pump 2 Fluid category 5 boosted water (CAT5B)BS B.02 vessel connection Fluid category 5 boosted water (CAT5B)35mm Cat 5 to pool water specialist plant and wash down points From BS B.02 to Pool plant and wash down Fluid category 5 boosted water (CAT5B)Isolation valve IV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Three port control valve 3PV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).Test point TP-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Strainer STR-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Test point TP-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Commissioning set CS-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Single pump P 0.01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).Drain off cock DOC-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Isolation valve IV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Drain off cock DOC-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Visual pressure gauge PG-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))PFlexible connection FC-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))Flexible connection FC-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))Visual pressure gauge PG-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))PAutomatic air vent AAV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.Flow switch FS-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).F/SIsolation valve IV-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))Isolation valve IV-A04 On ASHP 0.01 flushing bypass Normally closed flushing bypass across the heat pump connections.Isolation valve IV-A05 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Three port control valve 3PV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).Test point TP-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Strainer STR-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Test point TP-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Commissioning set CS-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Single pump P 0.02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).Drain off cock DOC-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Isolation valve IV-A06 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Drain off cock DOC-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Visual pressure gauge PG-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))PFlexible connection FC-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))Flexible connection FC-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))Visual pressure gauge PG-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))PAutomatic air vent AAV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.Flow switch FS-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).F/SIsolation valve IV-A07 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))Isolation valve IV-A08 On ASHP 0.02 flushing bypass Normally closed flushing bypass across the heat pump connections.Isolation valve IV-A09 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Three port control valve 3PV-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).Test point TP-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Strainer STR-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Test point TP-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Commissioning set CS-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Single pump P 0.03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).Drain off cock DOC-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Isolation valve IV-A10 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Drain off cock DOC-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Visual pressure gauge PG-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))PFlexible connection FC-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))Flexible connection FC-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))Visual pressure gauge PG-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))PAutomatic air vent AAV-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.Flow switch FS-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).F/SIsolation valve IV-A11 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))Isolation valve IV-A12 On ASHP 0.03 flushing bypass Normally closed flushing bypass across the heat pump connections.BMS temperature sensor T-A01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel)) BMS temperature sensor, ASHP common flow.TVisual temperature gauge TG-A01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel))TIsolation valve IV-A13 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel))Isolation valve IV-A14 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel))Visual temperature gauge TG-A02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel))TBMS temperature sensor T-A02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel)) BMS temperature sensor, ASHP common return.TIsolation valve IV-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow from the thermal store to the dirt separator (45°C))Isolation valve IV-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow from the thermal store to the dirt separator (45°C))Isolation valve IV-P03 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C))BMS temperature sensor T-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C)) BMS temperature sensor, primary flow into the low loss header.TFlow switch FS-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C)) Flow device on the primary flow (F on the record, COMMS to BMS).F/SIsolation valve IV-P04 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C))Isolation valve IV-P05 On Dosing pot connection from the primary flowIsolation valve IV-P06 On Dosing pot connection to the primary returnIsolation valve IV-P07 On Capped off connection on the low loss header (flow side)Commissioning set CS-P01 On Capped off connection on the low loss header (return side)Commissioning set CS-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) Sets and measures the primary flow back to the thermal store.Isolation valve IV-P08 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Test point TP-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Strainer STR-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Test point TP-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Visual pressure gauge PG-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))PTest point TP-P03 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Twin pump, duty and standby P B.01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) Lowara twin head pump between the low loss header and the thermal store.Test point TP-P04 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Visual pressure gauge PG-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))PIsolation valve IV-P09 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Visual temperature gauge TG-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))TBMS temperature sensor T-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) BMS temperature sensor, primary return to the thermal store.TIsolation valve IV-P10 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))Isolation valve IV-F01 On Pressurisation unit pump 1Single pump PU 0.01 pump 1 On Pressurisation unit pump 1Isolation valve IV-F02 On Pressurisation unit pump 1Isolation valve IV-F03 On Pressurisation unit pump 2Single pump PU 0.01 pump 2 On Pressurisation unit pump 2Isolation valve IV-F04 On Pressurisation unit pump 2BMS temperature sensor T-F01 On Pressurisation unit discharge to the low loss header Pressure device on the pressurisation unit discharge (unlabelled on the record).TBMS temperature sensor T-F02 On Pressurisation unit discharge to the low loss header Pressure device on the pressurisation unit discharge (unlabelled on the record).TNon return valve NRV-F01 On Pressurisation unit discharge to the low loss headerIsolation valve IV-F05 On Pressurisation unit discharge to the low loss headerIsolation valve IV-F06 On Pressurisation unit discharge to the low loss headerIsolation valve IV-F07 On Tank cold water service to the pressurisation unit tank and quick fill loopDouble check valve DCV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loopLockshield valve LSV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loopPressure reducing valve PRV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loopFlexible connection FC-F01 On Tank cold water service to the pressurisation unit tank and quick fill loop Removable quick fill loop from the tank cold water service, with PRV.Isolation valve IV-F08 On Tank cold water service to the pressurisation unit tank and quick fill loopIsolation valve IV-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Strainer STR-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Visual pressure gauge PG-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)PTest point TP-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Twin pump, duty and standby P B.02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Test point TP-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Visual pressure gauge PG-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)PIsolation valve IV-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)Visual temperature gauge TG-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)TDrain off cock DOC-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser) Flushing valve on the secondary flow.Commissioning set CS-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)Visual temperature gauge TG-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)TVisual pressure gauge PG-H03 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)PDrain off cock DOC-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header) Flushing valve on the circuit return.Isolation valve IV-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)Test point TP-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)Strainer STR-H02 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)Test point TP-H04 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)Automatic air vent AAV-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)Flexible connection FC-H02 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)Drain off cock DOC-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)Pressure independent control valve PICV-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return) Controls the AHU R.02 heating coil output and limits its flow (COMMS to BMS).Test point TP-H05 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)Isolation valve IV-H04 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)Isolation valve IV-H05 On AHU R.02 flushing bypassIsolation valve IV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)Test point TP-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)Strainer STR-H03 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)Test point TP-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)Automatic air vent AAV-H02 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H03 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)Flexible connection FC-H04 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)Drain off cock DOC-H04 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)Pressure independent control valve PICV-H02 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return) Controls the AHU R.08 heating coil output and limits its flow (COMMS to BMS).Test point TP-H08 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)Isolation valve IV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)Isolation valve IV-H08 On AHU R.08 flushing bypassIsolation valve IV-H09 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)Test point TP-H09 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)Strainer STR-H04 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)Test point TP-H10 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)Automatic air vent AAV-H03 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H05 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)Flexible connection FC-H06 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)Drain off cock DOC-H05 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)Pressure independent control valve PICV-H03 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return) Controls the AHU R.07 heating coil output and limits its flow (COMMS to BMS).Test point TP-H11 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)Isolation valve IV-H10 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)Isolation valve IV-H11 On AHU R.07 flushing bypassIsolation valve IV-H12 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)Test point TP-H12 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)Strainer STR-H05 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)Test point TP-H13 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)Automatic air vent AAV-H04 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H07 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)Flexible connection FC-H08 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)Drain off cock DOC-H06 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)Pressure independent control valve PICV-H04 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return) Controls the AHU R.01 heating coil output and limits its flow (COMMS to BMS).Test point TP-H14 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)Isolation valve IV-H13 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)Isolation valve IV-H14 On AHU R.01 flushing bypassIsolation valve IV-H15 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)Test point TP-H15 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)Strainer STR-H06 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)Test point TP-H16 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)Automatic air vent AAV-H05 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H09 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)Flexible connection FC-H10 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)Drain off cock DOC-H07 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)Pressure independent control valve PICV-H05 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return) Controls the AHU R.04 heating coil output and limits its flow (COMMS to BMS).Test point TP-H17 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)Isolation valve IV-H16 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)Isolation valve IV-H17 On AHU R.04 flushing bypassIsolation valve IV-H18 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)Test point TP-H18 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)Strainer STR-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)Test point TP-H19 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)Automatic air vent AAV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H11 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)Flexible connection FC-H12 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)Drain off cock DOC-H08 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)Pressure independent control valve PICV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return) Controls the AHU R.09 heating coil output and limits its flow (COMMS to BMS).Test point TP-H20 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)Isolation valve IV-H19 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)Isolation valve IV-H20 On AHU R.09 flushing bypassIsolation valve IV-H21 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)Test point TP-H21 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)Strainer STR-H08 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)Three port control valve 3PV-H01 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow) Motorised three port valve with DRV bypass to the return leg (COMMS to BMS).Test point TP-H22 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)Flexible connection FC-H13 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)Flexible connection FC-H14 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)Drain off cock DOC-H09 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)Test point TP-H23 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)Isolation valve IV-H22 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)Isolation valve IV-H23 On AHU R.05 flushing bypassDouble regulating valve DRV-H01 On AHU R.05 three port valve bypassIsolation valve IV-H24 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)Test point TP-H24 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)Strainer STR-H09 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)Test point TP-H25 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)Automatic air vent AAV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H15 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)Flexible connection FC-H16 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)Drain off cock DOC-H10 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)Pressure independent control valve PICV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return) Controls the AHU R.03 heating coil output and limits its flow (COMMS to BMS).Test point TP-H26 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)Isolation valve IV-H25 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)Isolation valve IV-H26 On AHU R.03 flushing bypassIsolation valve IV-H27 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)Test point TP-H27 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)Strainer STR-H10 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)Test point TP-H28 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)Automatic air vent AAV-H08 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow) Automatic air vent with isolating valve at the coil connection.Flexible connection FC-H17 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)Flexible connection FC-H18 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)Drain off cock DOC-H11 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)Pressure independent control valve PICV-H08 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return) Controls the AHU R.06 heating coil output and limits its flow (COMMS to BMS).Test point TP-H29 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)Isolation valve IV-H28 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)Isolation valve IV-H29 On AHU R.06 flushing bypassIsolation valve IV-H30 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)Test point TP-H30 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)Pressure independent control valve PICV-H09 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow) Controls the dry change reheat coil (COMMS to BMS). Drawn on the flow leg on the record.Drain off cock DOC-H12 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)Flexible connection FC-H19 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)Flexible connection FC-H20 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Automatic air vent AAV-H09 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Test point TP-H31 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Strainer STR-H11 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Test point TP-H32 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Isolation valve IV-H31 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)Isolation valve IV-H32 On HB 0.01 flushing bypassIsolation valve IV-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Strainer STR-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Visual pressure gauge PG-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)PTest point TP-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Twin pump, duty and standby P B.03 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Test point TP-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Visual pressure gauge PG-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)PIsolation valve IV-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)Visual temperature gauge TG-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)TDrain off cock DOC-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03) Flushing valve on the secondary flow.Commissioning set CS-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)Visual temperature gauge TG-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)TVisual pressure gauge PG-L03 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)PDrain off cock DOC-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header) Flushing valve on the circuit return.Isolation valve IV-L03 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)Visual pressure gauge PG-L04 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)PStrainer STR-L02 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)Visual pressure gauge PG-L05 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)PTest point TP-L03 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)Three port control valve 3PV-L01 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger return) Motorised three port valve with DRV bypass from the flow leg (COMMS to BMS).Isolation valve IV-L04 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger return)Isolation valve IV-L05 On 160 kW main pool plate heat exchanger flushing bypassDouble regulating valve DRV-L01 On 160 kW main pool plate heat exchanger three port valve bypassSingle pump PHE main pool pool pump On 160 kW main pool plate heat exchanger, pool water side (by others)BMS temperature sensor T-X01 On 160 kW main pool plate heat exchanger, pool water side (by others) Pool water temperature sensor (COMMS).TBMS temperature sensor T-X02 On 160 kW main pool plate heat exchanger, pool water side (by others) Pool water high temperature sensor (COMMS).TIsolation valve IV-L06 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)Visual pressure gauge PG-L06 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)PStrainer STR-L03 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)Visual pressure gauge PG-L07 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)PTest point TP-L04 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)Pressure independent control valve PICV-L01 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger return) Controls the learner pool plate heat exchanger (COMMS to BMS).Isolation valve IV-L07 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger return)Isolation valve IV-L08 On 40 kW learner pool plate heat exchanger flushing bypassSingle pump PHE learner pool pool pump On 40 kW learner pool plate heat exchanger, pool water side (by others)BMS temperature sensor T-X03 On 40 kW learner pool plate heat exchanger, pool water side (by others) Pool water temperature sensor (COMMS).TBMS temperature sensor T-X04 On 40 kW learner pool plate heat exchanger, pool water side (by others) Pool water high temperature sensor (COMMS).TIsolation valve IV-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Strainer STR-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Visual pressure gauge PG-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)PTest point TP-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Twin pump, duty and standby P B.04 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Test point TP-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Visual pressure gauge PG-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)PIsolation valve IV-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)Visual temperature gauge TG-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)TDrain off cock DOC-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04) Flushing valve on the secondary flow.Commissioning set CS-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)Visual temperature gauge TG-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)TVisual pressure gauge PG-W03 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)PDrain off cock DOC-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header) Flushing valve on the circuit return.Isolation valve IV-W03 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil flow)Automatic air vent AAV-W01 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil flow)Drain off cock DOC-W03 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil return)Isolation valve IV-W04 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil return)Isolation valve IV-W05 On WH B.01 flushing bypassThree port control valve 3PV-D01 On WH B.01 hot water outlet Valve on the cylinder hot outlet with a discharge branch through a tundish (T) to low level for drain.Visual temperature gauge TG-D01 On WH B.01 hot water outletTIsolation valve IV-W06 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil flow)Automatic air vent AAV-W02 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil flow)Drain off cock DOC-W04 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil return)Isolation valve IV-W07 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil return)Isolation valve IV-W08 On WH B.02 flushing bypassThree port control valve 3PV-D02 On WH B.02 hot water outlet Valve on the cylinder hot outlet with a discharge branch through a tundish (T) to low level for drain.Isolation valve IV-D01 On Cold feed to WH B.01 with expansion vessel and relief valveSafety / expansion relief valve SV-D01 On Cold feed to WH B.01 with expansion vessel and relief valveIsolation valve IV-D02 On Cold feed to WH B.02 with expansion vessel and relief valveSafety / expansion relief valve SV-D02 On Cold feed to WH B.02 with expansion vessel and relief valveIsolation valve IV-D03 On Hot water secondary return via P B.05Visual temperature gauge TG-D02 On Hot water secondary return via P B.05TStrainer STR-D01 On Hot water secondary return via P B.05Single pump P B.05 On Hot water secondary return via P B.05Non return valve NRV-D01 On Hot water secondary return via P B.05Isolation valve IV-D04 On Hot water secondary return via P B.05Isolation valve IV-D05 On 54mm boosted cold water feed to the hot water heaters via PRVStrainer STR-D02 On 54mm boosted cold water feed to the hot water heaters via PRVPressure reducing valve PRV-D01 On 54mm boosted cold water feed to the hot water heaters via PRVNon return valve NRV-D02 On 54mm boosted cold water feed to the hot water heaters via PRVIsolation valve IV-D06 On 54mm boosted cold water feed to the hot water heaters via PRVIsolation valve IV-C01 On Existing tank cold water down service to BS B.01 suctionIsolation valve IV-C02 On BS B.01 pump 1Single pump BS B.01 pump 1 On BS B.01 pump 1Isolation valve IV-C03 On BS B.01 pump 1Isolation valve IV-C04 On BS B.01 pump 2Single pump BS B.01 pump 2 On BS B.01 pump 2Isolation valve IV-C05 On BS B.01 pump 2Isolation valve IV-C06 On BS B.01 pump 3Single pump BS B.01 pump 3 On BS B.01 pump 3Isolation valve IV-C07 On BS B.01 pump 3Visual temperature gauge TG-C01 On Boosted cold water from BS B.01TVisual pressure gauge PG-C01 On Boosted cold water from BS B.01PIsolation valve IV-C08 On Boosted cold water from BS B.01Non return valve NRV-C01 On Boosted cold water from BS B.01Strainer STR-C01 On Boosted cold water from BS B.01Pressure reducing valve PRV-C01 On Boosted cold water from BS B.01Isolation valve IV-C09 On Boosted cold water from BS B.01Safety / expansion relief valve SV-C01 On Boosted cold water from BS B.01Isolation valve IV-C10 On Boosted cold water from BS B.01Visual temperature gauge TG-C02 On Boosted cold water from BS B.01TVisual pressure gauge PG-C02 On Boosted cold water from BS B.01PIsolation valve IV-C11 On Boosted cold water from BS B.01Isolation valve IV-C12 On BCWS riser (76mm)Isolation valve IV-C13 On 22mm BCWS to serve the heating system pressurisation unitIsolation valve IV-C14 On 35mm BCWS to the Cat 5 break tank (BS B.02)Isolation valve IV-C15 On 35mm BCWS to the Cat 5 break tank (BS B.02)Isolation valve IV-K01 On Cat 5 break tank outlet to BS B.02 pumpsIsolation valve IV-K02 On BS B.02 pump 1Single pump BS B.02 pump 1 On BS B.02 pump 1Isolation valve IV-K03 On BS B.02 pump 1Isolation valve IV-K04 On BS B.02 pump 2Single pump BS B.02 pump 2 On BS B.02 pump 2Isolation valve IV-K05 On BS B.02 pump 2Visual temperature gauge TG-K01 On 35mm Cat 5 to pool water specialist plant and wash down pointsTVisual pressure gauge PG-K01 On 35mm Cat 5 to pool water specialist plant and wash down pointsPIsolation valve IV-K06 On 35mm Cat 5 to pool water specialist plant and wash down pointsNon return valve NRV-K01 On 35mm Cat 5 to pool water specialist plant and wash down pointsIsolation valve IV-K07 On 35mm Cat 5 to pool water specialist plant and wash down pointsASHP 0.01 Packaged air source heat pump c/w integral heat metering and controls sequencer MCCASHP 0.02 Packaged air source heat pump c/w integral heat metering and controls sequencer MCCASHP 0.03 Packaged air source heat pump c/w integral heat metering and controls sequencer MCCTS B.01 LTHW thermal store Dirt/air separator Dirt and air separator on the primary flow Chemical dosing pot Chemical dosing pot (bypass across primary flow and return) Low loss header 300mmØ low loss header PU 0.01 Packaged pressurisation unit and expansion vessel PU 0.01 vessel 1 Expansion vessel (pressurisation package) PU 0.01 vessel 2 Expansion vessel (pressurisation package) AHU R.02 Wet Change Air Handling Unit AHUR.02AHU R.08 Fitness Studio AHUR.08AHU R.07 Sports Hall Air Handling Unit AHUR.07AHU R.01 Pool Air Handling Unit AHUR.01AHU R.04 Dance Studio Air Handling Unit AHUR.04AHU R.09 Squash Court And Viewing AHUR.09AHU R.05 Soft Play Air Handling Unit AHUR.05AHU R.03 Foh & Ancillaries Air Handling Unit AHUR.03AHU R.06 Spin Studio Air Handling Unit AHUR.06HB 0.01 Dry change reheat coil HB0.01PHE main pool 160 kW main pool plate heat exchanger PHE learner pool 40 kW learner pool plate heat exchanger WH B.01 Packaged 1000L hot water storage heater c/w 38kW primary heating coil and immersion heaters WH B.02 Packaged 1000L hot water storage heater c/w 38kW primary heating coil and immersion heaters EV (WH B.01) Potable expansion vessel, WH B.01 unvented kit EV (WH B.02) Potable expansion vessel, WH B.02 unvented kit BS B.01 vessel Booster set expansion vessel (BS B.01) Water conditioner Water conditioner (scale reducer) BS B.02 Cat 5 packaged break tank and booster set c/w expansion vessel for pool plant and wash down BS B.02 vessel Cat 5 booster set expansion vessel (BS B.02) TCWS54mmØ HWS35mmØ HWS R54mmØ BCWSDISCHARGE POINTTO SERVE HEATING SYSTEM PRESSURISATION UNIT76mmØ BCWSIVTPSTTPCSDCIVDCFCFCAAVFIVFBIVTPSTTPCSDCIVDCFCFCAAVFIVFBIVTPSTTPCSDCIVDCFCFCAAVFIVFBTIVIVTIVIVIVTFIVIVIVIVDRV/OPDRV/OPIVTPSTRTPTPTPIVTIVIVIVIVIVNRVIVIVIVDCVLSVPRVIVIVSTRTPTPIVCSIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTR3PVTPFCFCTPIVFBDRVIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPSTRTPAAVFCFCDOCPICVTPIVFBIVTPPICVDOCFCFCAAVTPSTRTPIVFBIVSTRTPTPIVCSIVSTRTP3PVIVIVDRVTHTIVSTRTPPICVIVIVTHTIVSTRTPTPIVCSIVAAVDOCIVFBIVAAVDOCIVFBIVSVIVSVIVSTRNRVIVIVSTRPRVNRVIVIVIVIVIVIVIVIVIVNRVSTPRVIVIVIVIVIVIVIVIVIVIVIVIVIVNRVIVBMS temperature sensor 1 of 4 on the thermal store (COMMS to BMS).TBMS temperature sensor 2 of 4 on the thermal store (COMMS to BMS).TBMS temperature sensor 3 of 4 on the thermal store (COMMS to BMS).TBMS temperature sensor 4 of 4 on the thermal store (COMMS to BMS).TBMS temperature sensor on the low loss header (COMMS to BMS).TBMS temperature sensor at the base of the low loss header (COMMS to BMS).TCOMMSCOMMSCOMMSBMSBMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMSCOMMS13.20 kg/s160mmØ1.01 m/s61 Pa/m13.20 kg/s160mmØ1.01 m/s61 Pa/m2.5 kg/s63mmØ1.24 m/s276 Pa/m26.4 kg/s180mmØ1.59 m/s123 Pa/m28.9 kg/s180mmØ1.74 m/s146 Pa/m28.9 kg/s150mmØ1.56 m/s128 Pa/m27.26 kg/s150mmØ1.49 m/s121 Pa/m27.26 kg/s150mmØ1.49 m/s121 Pa/m16.980 kg/s150mmØ0.89 m/s44 Pa/m17.810 kg/s150mmØ0.95 m/s48 Pa/m18.261 kg/s150mmØ0.99 m/s51.5 Pa/m2.109 kg/s50mmØ0.96 m/s191 Pa/m0.670 kg/s32mmØ0.71 m/s152 Pa/m14.870 kg/s100mmØ1.73 m/s285 Pa/m5.416 kg/s65mmØ1.47 m/s311 Pa/m14.200 kg/s100mmØ1.65 m/s225 Pa/m7.674 kg/s80mmØ1.51 m/s268 Pa/m8.784 kg/s100mmØ1.06 m/s90 Pa/m0.21 kg/s20mmØ0.57 m/s220 Pa/m1.110 kg/s40mmØ0.88 m/s180 Pa/m0.530 kg/s32mmØ0.61 m/s97 Pa/m0.900 kg/s32mmØ0.96 m/s265 Pa/m0.370 kg/s25mmØ0.62 m/s198 Pa/m0.650 kg/s32mmØ0.73 m/s141 Pa/m0.180 kg/s20mmØ0.5 m/s163 Pa/m0.830 kg/s32mmØ0.91 m/s227 Pa/m0.451 kg/s25mmØ0.74 m/s290 Pa/m6.599 kg/s80mmØ1.31 m/s201 Pa/m5.443 kg/s65mmØ1.48 m/s314 Pa/m1.157 kg/s40mmØ0.85 m/s200 Pa/m2.538 kg/s50mmØ1.16 m/s271 Pa/m1.269 kg/s40mmØ0.95 m/s248 Pa/m1.269 kg/s40mmØ0.95 m/s248 Pa/m76mmØ--BCWS22mmØ--BCWS35mmØ--BCWSASHP PRIMARY FLOW (45'C)ASHP PRIMARY RETURN (38'C)MECHANICAL CONTROLPANEL INTEGRATED TO ASHPBY MANUFACTURER.PACKAGED AIR SOURCE HEAT PUMPc/w INTEGRAL HEAT METERING ANDCONTROLS SEQUENCERBMSASHP PRIMARY FLOW (45'C)ASHP PRIMARY RETURN (38'C)MECHANICAL CONTROLPANEL INTEGRATED TO ASHPBY MANUFACTURER.PACKAGED AIR SOURCE HEAT PUMPc/w INTEGRAL HEAT METERING ANDCONTROLS SEQUENCERBMSASHP PRIMARY FLOW (45'C)ASHP PRIMARY RETURN (38'C)MECHANICAL CONTROLPANEL INTEGRATED TO ASHPBY MANUFACTURER.PACKAGED AIR SOURCE HEAT PUMPc/w INTEGRAL HEAT METERING ANDCONTROLS SEQUENCERBMSEXTERNAL BELOW GROUNDPIPEWORKPREINSULATED MDPE MAINSINTERNAL PIPEWORK STEELTUBE AND FITTINGSLTHWTHERMALSTOREASHP PRIMARY FLOW (45'C)DIRT/AIRSEPERATORAAVDCCHEMICALDOSING POTIVDC300mmØ LOW LOSS HEADERAAVDC300mmØ LOW LOSS HEADER SIZED TOSUIT SECONDARY SIDE OF THE HEATINGSYSTEMCAPPED OFFCONNECTIONCAPPED OFFCONNECTIONASHP PRIMARY RETURN (38'C)TANKEXPANSIONVESSELSPACKAGED PRESSURISATION UNITAND EXPANSION VESSELREMOVABLEQUICK FILLLOOPOVERFLOW45'C45'C45'C38'C38'C38'CFLUSHINGVALVEFLUSHINGVALVEFLUSHINGVALVEFLUSHINGVALVEFLUSHINGVALVEFLUSHINGVALVEALL SECONDARY CIRCUITS AT 45'C / 38'CFLOW AND RETURN WATERTEMPERATURESWET CHANGEAIR HANDLING UNITFITNESS STUDIOSPORTS HALLAIR HANDLING UNITPOOLAIR HANDLING UNITDANCE STUDIOAIR HANDLING UNITSQUASH COURT ANDVIEWINGSOFT PLAYAIR HANDLING UNITFOH & ANCILLARIESAIR HANDLING UNITSPIN STUDIOAIR HANDLING UNITDRY CHANGEREHEAT COILFLUSHINGBYPASS160 kW MAIN POOLPLATE HEATEXCHANGER(BY OTHERS)FLUSHINGBYPASS40 kW LEARNER POOLPLATE HEATEXCHANGER(BY OTHERS)TTO LL FORDRAINPACKAGED 1000L HOT WATERSTORAGE HEATER c/w 38kWPRIMARY HEATING COIL ANDIMMERSION HEATERSTTO LL FORDRAINPACKAGED 1000L HOT WATERSTORAGE HEATER c/w 38kWPRIMARY HEATING COIL ANDIMMERSION HEATERSEVEVCONNECT TO PACKAGE HOTWATER HEATERCONNECT TO PACKAGE HOTWATER HEATERCONNECT TO PACKAGE HOTWATER HEATERCONNECT TO PACKAGE HOTWATER HEATEREXISTING TANKCOLD WATERDOWN SERVICEBOOSTER SET C/WEXPANSION VESSELBCWSWATERCONDITIONERACCESSHATCHOVERFLOWHIGH LEVEL ALARMLOW LEVEL ALARMDCCAT 5 PACKAGED BREAK TANK & BOOSTERSET C/W EXPANSION VESSEL FOR POOLPLANT AND WASH DOWN35mmØ CAT 5 TOPOOL WATERSPECIALIST PLANT &WASH DOWN POINTSTHE INFORMATION SHOWN ON THIS DRAWING IS DESIGNINTENT AT THE CURRENT DESIGN STAGE ONLY AND SHALLBE SUBJECT TO DETAILED DESIGN AND SUPPORTINGCALCULATIONS BY THE MECHANICAL AND ELECTRICALSERVICES CONTRACTOR UNDER A DESIGN AND BUILDAPPOINTMENT TO REFLECT ANY DEVELOPMENT ANDPROCURED PLANT. ROUTES AND SIZES SHOWN HAVE BEENUSED FOR PRELIMINARY COORDINATION PURPOSES ONLY.ASHP0.01P0.01ASHP0.02P0.02ASHP0.03P0.03TSB.01PB.01PB.02PB.03PB.04WHB.01WHB.02PB.05BSB.01BSB.02COPYRIGHTTHIS DRAWING IS COPYRIGHT AND MAY NOT BE ALTERED, REPRODUCED OR USEDOTHER THAN FOR THE CONTRACT WORKS FOR WHICH IT IS ISSUED WITHOUT THEWRITTEN PERMISSION OF HDN|MEP LTD.WARNINGDO NOT SCALE OFF THIS DRAWING.VERIFY ALL DIMENSIONS AND STRUCTURAL DETAILS ON SITE.IF IN DOUBT, ASK BEFORE ACTING.RELATED DOCUMENTSREAD THIS DRAWING IN CONJUNCTION WITH THE APPROPRIATE SPECIFICATION(S).CHECKINGTHIS DRAWING HAS BEEN GENERATED USING A COMPUTER AIDED DRAWING SYSTEM, ASTHE SYSTEM GENERATES A NEW DRAWING AT EACH REVISION ONLY THE LATESTEDITION WILL HAVE BEEN CHECKED.GENERAL NOTES1.THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS,SPECIFICATIONS AND SCHEDULES.2.ALL EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE SLAB /STRUCTURE AND NOT BE RELIANT ON THE CEILING OR OTHER SERVICES.3.ALL PENETRATIONS THROUGH WALL SHALL BE FILLED TO SUIT THE ACOUSTICPERFORMANCE AND / OR THE FIRE REQUIREMENTS AS DETAILED ON THEARCHITECT'S DRAWINGS.4.ALL FINAL CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THEMANUFACTURER'S RECOMMENDATIONS.HEATING SERVICES NOTES1.PRIOR TO INSTALLATION, THE CONTRACTOR SHALL ENSURE FINAL COORDINATIONOF EMITTERS, PIPEWORK AND VALVES WITH THE FINAL FURNITURE LAYOUT.2.ALL LOW POINTS TO BE PROVIDED WITH DRAIN COCKS AND HIGH POINTS WITHAUTOMATIC AIR VENTS.3.ALL PIPEWORK TO BE INSULATED AND IDENTIFIED IN ACCORDANCE WITH BS EN6644:1991. INSULATION WITHIN SWIMMING POOL TO BE ISOGENOPAK FINISH,ELSEWHERE FOIL FACED FINISH.4.ALL FINAL CONNECTIONS SHALL BE 15mmØ FLOW AND RETURN UNLESS STATEDOTHERWISE5.SPECIFIC REFERENCE SHALL BE MADE TO THE SCHEMATIC DRAWINGS FOR VALVEARRANGEMENTS.COOLING SERVICES NOTES1.REFRIGERANT PIPEWORK SIZES AND SYSTEM REFRIGERANT VOLUME ARESPECIALIST DESIGN2.ALL PIPEWORK SHALL BE INSULATED AND VAPOUR SEALED THROUGHOUTPLANTROOM SERVICES LEGEND:ISOLATION VALVE (IV)COMMISSIONING SET (DRV / OP)FLUSHING BY-PASS VALVE (FB)STRAINER (ST / STR)2 PORT VALVE3 PORT VALVEPRESSURE INDEPENDENT CONTROL VALVETTHERMOSTATIC TEMPERATURE SENSOR (BMS)TTEMPERATURE GAUGEPPRESSURE GAUGENON RETURN VALVEFLEXIBLE CONNECTIONSINGLE HEAD PUMPTWIN HEAD PUMPPRIMARY SIDE LTHW PIPEWORKSECONDARY SIDE LTHW PIPEWORKBOOSTED / MAINS COLD WATER PIPEWORKCAT 5 BOOSTED WATER PIPEWORKDOMESTIC HOT WATER PIPEWORKPOOL WATER SIDE (BY OTHERS)AF01AS FITTED28.04.26MPODBP01PRELIMINARY ISSUExx.04.25MWDBREVDESCRIPTIONDATEDRAWNCHECKSTATUSAS FITTEDCLIENTWESTGATE LEISURE SERVICESPROJECTELMWOOD LEISURE CENTREDRAWING TITLEMECHANICAL SERVICESPRIMARY PLANT ROOM SCHEMATICSCALE @ A0N.T.SDRAWN BYMW1ST ISSUE DATEJUN '24CHECKED BYDBCOMPANY ADDRESSRoall Hall, Roall Lane,Eggborough, North Yorkshire,DN14 0NYDRAWINGS PRODUCED BYHensall Mechanical Services Ltd. www.hensall.comTel 01977 661318 Fax 01977 662127PROJECT ADDRESSElmwood Leisure CentreMarket Gate Road, Elmwood EL6 4QTJOB No.HEN0203DRG No.HEN0203-HEN-00-ZZ-DR-M-5991REV.AF01ASITE DOC REF.HEN0203-HEN-00-ZZ-DR-M-5991INTERACTIVE REPLICARedrawn by SF, 15.10.26, from AF01. No design change.
Pinch to zoom, drag to pan. Tap an item for its manual pages. Press and hold for more options.