Elmwood Leisure Centre · Primary Plant Room Schematic
HEN0203-HEN-00-ZZ-DR-M-5991 rev AF01 · As fitted record · O&M manual Vol 6 p126
Flow
Panel
Clickable schematic:
tap any item to see its manual pages or ask about it. Live BMS link: concept, coming soon.
ASHP 0.01 primary return riser (38°C) From ASHP return header to ASHP 0.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
ASHP 0.01 primary flow riser (45°C) From ASHP 0.01 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
ASHP 0.01 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP 0.01 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP 0.02 primary return riser (38°C) From ASHP return header to ASHP 0.02 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
ASHP 0.02 primary flow riser (45°C) From ASHP 0.02 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
ASHP 0.02 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP 0.02 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP 0.03 primary return riser (38°C) From ASHP return header to ASHP 0.03 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 2.5 kg/s, 63mm, 1.24 m/s, 276 Pa/m
ASHP 0.03 primary flow riser (45°C) From ASHP 0.03 to ASHP flow header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 2.5 kg/s, 63mm, 1.24 m/s, 276 Pa/m
ASHP 0.03 flushing bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP 0.03 three port valve bypass Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP flow header, ASHP 0.01 section From ASHP 0.01 to Header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
ASHP flow header, external MDPE From ASHP 0.01 and 0.02 to Header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 26.4 kg/s, 180mm, 1.59 m/s, 123 Pa/m
ASHP flow header, external preinsulated MDPE main From All ASHPs to Plant room Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 180mm, 1.74 m/s, 146 Pa/m
ASHP primary flow into the thermal store (internal steel) From ASHP flow header to TS B.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 150mm, 1.56 m/s, 128 Pa/m
ASHP primary return from the thermal store (internal steel) From TS B.01 to ASHP return header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 150mm, 1.56 m/s, 128 Pa/m
ASHP return header, external MDPE Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 28.9 kg/s, 180mm, 1.74 m/s, 146 Pa/m
ASHP return header, external MDPE Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 26.4 kg/s, 180mm, 1.59 m/s, 123 Pa/m
ASHP return header, ASHP 0.01 section Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 13.20 kg/s, 160mm, 1.01 m/s, 61 Pa/m
Primary flow from the thermal store to the dirt separator (45°C) From TS B.01 to Dirt/air separator Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/m
Primary flow to the low loss header (45°C) From Dirt/air separator to Low loss header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/m
Dosing pot connection from the primary flow Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Dosing pot connection to the primary return Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Capped off connection on the low loss header (flow side) Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Capped off connection on the low loss header (return side) Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
ASHP primary return, low loss header to thermal store (38°C) From Low loss header to TS B.01 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI) On the drawing: 27.26 kg/s, 150mm, 1.49 m/s, 121 Pa/m
Pressurisation unit pump suction from the tank Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Pressurisation unit pump 1 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Pressurisation unit pump 2 Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Pressurisation unit discharge to the low loss header From PU 0.01 to Low loss header Primary side LTHW pipework (ASHP primary, 45/38°C) (PRI)
Tank cold water service to the pressurisation unit tank and quick fill loop Boosted / mains cold water pipework (TCWS)
Tank cold water feed to the pressurisation unit tank float valve Boosted / mains cold water pipework (TCWS)
AHU constant temperature flow, P B.02 to the AHU riser From Low loss header to AHU flow riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 18.261 kg/s, 150mm, 0.99 m/s, 51.5 Pa/m
AHU flow riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 17.810 kg/s, 150mm, 0.95 m/s, 48 Pa/m
AHU flow riser to the roof header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/m
AHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/m
AHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 17.810 kg/s, 150mm, 0.95 m/s, 48 Pa/m
AHU constant temperature return to the low loss header From AHU return riser to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 18.261 kg/s, 150mm, 0.99 m/s, 51.5 Pa/m
AHU R.02 coil flow From AHU flow header to AHU R.02 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.109 kg/s, 50mm, 0.96 m/s, 191 Pa/m
AHU R.02 coil return From AHU R.02 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.109 kg/s, 50mm, 0.96 m/s, 191 Pa/m
AHU R.02 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 16.980 kg/s, 150mm, 0.89 m/s, 44 Pa/m
AHU R.08 coil flow From AHU flow header to AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.670 kg/s, 32mm, 0.71 m/s, 152 Pa/m
AHU R.08 coil return From AHU R.08 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.670 kg/s, 32mm, 0.71 m/s, 152 Pa/m
AHU R.08 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.870 kg/s, 100mm, 1.73 m/s, 285 Pa/m
AHU return header from AHU R.08 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.870 kg/s, 100mm, 1.73 m/s, 285 Pa/m
AHU R.07 coil flow From AHU flow header to AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.416 kg/s, 65mm, 1.47 m/s, 311 Pa/m
AHU R.07 coil return From AHU R.07 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.416 kg/s, 65mm, 1.47 m/s, 311 Pa/m
AHU R.07 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.200 kg/s, 100mm, 1.65 m/s, 225 Pa/m
AHU return header from AHU R.07 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 14.200 kg/s, 100mm, 1.65 m/s, 225 Pa/m
AHU R.01 coil flow From AHU flow header to AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 7.674 kg/s, 80mm, 1.51 m/s, 268 Pa/m
AHU R.01 coil return From AHU R.01 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 7.674 kg/s, 80mm, 1.51 m/s, 268 Pa/m
AHU R.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 8.784 kg/s, 100mm, 1.06 m/s, 90 Pa/m
AHU return header from AHU R.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 8.784 kg/s, 100mm, 1.06 m/s, 90 Pa/m
AHU R.04 coil flow From AHU flow header to AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.21 kg/s, 20mm, 0.57 m/s, 220 Pa/m
AHU R.04 coil return From AHU R.04 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.21 kg/s, 20mm, 0.57 m/s, 220 Pa/m
AHU R.04 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.110 kg/s, 40mm, 0.88 m/s, 180 Pa/m
AHU return header from AHU R.04 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.110 kg/s, 40mm, 0.88 m/s, 180 Pa/m
AHU R.09 coil flow From AHU flow header to AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.530 kg/s, 32mm, 0.61 m/s, 97 Pa/m
AHU R.09 coil return From AHU R.09 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.530 kg/s, 32mm, 0.61 m/s, 97 Pa/m
AHU R.09 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.900 kg/s, 32mm, 0.96 m/s, 265 Pa/m
AHU return header from AHU R.09 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.900 kg/s, 32mm, 0.96 m/s, 265 Pa/m
AHU R.05 coil flow From AHU flow header to AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/m
AHU R.05 coil return From AHU R.05 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/m
AHU R.05 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU R.05 three port valve bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU flow header to AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/m
AHU return header from AHU R.05 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.370 kg/s, 25mm, 0.62 m/s, 198 Pa/m
AHU R.03 coil flow From AHU flow header to AHU R.03 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/m
AHU R.03 coil return From AHU R.03 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/m
AHU R.03 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
AHU R.06 coil flow From AHU flow header to AHU R.06 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.180 kg/s, 20mm, 0.5 m/s, 163 Pa/m
AHU R.06 coil return From AHU R.06 to AHU return header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.180 kg/s, 20mm, 0.5 m/s, 163 Pa/m
AHU R.06 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
FOH and spin studio AHU flow Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.830 kg/s, 32mm, 0.91 m/s, 227 Pa/m
FOH AHU flow Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/m
FOH AHU return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.650 kg/s, 32mm, 0.73 m/s, 141 Pa/m
FOH and spin studio AHU return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.830 kg/s, 32mm, 0.91 m/s, 227 Pa/m
HB 0.01 dry change reheat coil flow From AHU flow riser to HB 0.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.451 kg/s, 25mm, 0.74 m/s, 290 Pa/m
HB 0.01 dry change reheat coil return From HB 0.01 to AHU return riser Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 0.451 kg/s, 25mm, 0.74 m/s, 290 Pa/m
HB 0.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
Pool plate heat exchanger flow, P B.03 From Low loss header to Pool plate heat exchangers Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 6.599 kg/s, 80mm, 1.31 m/s, 201 Pa/m
Pool plate heat exchanger return to the low loss header From Pool plate heat exchangers to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 6.599 kg/s, 80mm, 1.31 m/s, 201 Pa/m
160 kW main pool plate heat exchanger flow From Pool circuit to PHE main pool Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.443 kg/s, 65mm, 1.48 m/s, 314 Pa/m
160 kW main pool plate heat exchanger return From PHE main pool to Pool circuit return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 5.443 kg/s, 65mm, 1.48 m/s, 314 Pa/m
160 kW main pool plate heat exchanger flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
160 kW main pool plate heat exchanger three port valve bypass Secondary side LTHW pipework (45/38°C) (SEC)
160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
160 kW main pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
Learner pool plate heat exchanger flow branch Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m
40 kW learner pool plate heat exchanger flow From Pool circuit to PHE learner pool Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m
40 kW learner pool plate heat exchanger return From PHE learner pool to Pool circuit return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m
40 kW learner pool plate heat exchanger flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
40 kW learner pool plate heat exchanger, pool water side (by others) Pool water side, by others (POOLX)
Learner pool plate heat exchanger return branch Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.157 kg/s, 40mm, 0.85 m/s, 200 Pa/m
Hot water heater primary flow, P B.04 From Low loss header to HWH B.01 and B.02 coils Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.538 kg/s, 50mm, 1.16 m/s, 271 Pa/m
Hot water heater primary return to the low loss header From HWH coils to Low loss header Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 2.538 kg/s, 50mm, 1.16 m/s, 271 Pa/m
WH B.01 primary coil flow From Hot water heater primary to WH B.01 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/m
WH B.01 primary coil return From WH B.01 to Hot water heater primary return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/m
WH B.01 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
WH B.01 hot water outlet From WH B.01 to 54mm HWS Domestic hot water pipework (DHW)
WH B.01 relief discharge to low level drain Domestic hot water pipework (DHW)
WH B.02 primary coil flow From Hot water heater primary to WH B.02 Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/m
WH B.02 primary coil return From WH B.02 to Hot water heater primary return Secondary side LTHW pipework (45/38°C) (SEC) On the drawing: 1.269 kg/s, 40mm, 0.95 m/s, 248 Pa/m
WH B.02 flushing bypass Secondary side LTHW pipework (45/38°C) (SEC)
WH B.02 hot water outlet From WH B.02 to 54mm HWS Domestic hot water pipework (DHW)
WH B.02 relief discharge to low level drain Domestic hot water pipework (DHW)
Cold feed to WH B.01 with expansion vessel and relief valve From Cold feed to WH B.01 Domestic hot water pipework (DHW)
Cold feed to WH B.02 with expansion vessel and relief valve From Cold feed to WH B.02 Domestic hot water pipework (DHW)
Expansion vessel connection, WH B.01 Domestic hot water pipework (DHW)
Expansion vessel connection, WH B.02 Domestic hot water pipework (DHW)
Cold feed and secondary return to the hot water heaters From 54mm BCWS / 35mm HWS R to WH B.01 and B.02 Domestic hot water pipework (DHW)
Hot water secondary return via P B.05 From 35mm HWS R to Hot water heaters Domestic hot water pipework (DHW)
54mm boosted cold water feed to the hot water heaters via PRV From 54mm BCWS to Hot water heaters Boosted / mains cold water pipework (TCWS)
Existing tank cold water down service to BS B.01 suction From Existing tank to BS B.01 Boosted / mains cold water pipework (TCWS)
BS B.01 pump 1 Boosted / mains cold water pipework (TCWS)
BS B.01 pump 2 Boosted / mains cold water pipework (TCWS)
BS B.01 pump 3 Boosted / mains cold water pipework (TCWS)
Boosted cold water from BS B.01 From BS B.01 to Water conditioner Boosted / mains cold water pipework (TCWS)
Relief valve discharge to the discharge point Relief valve discharge (DISCH)
BCWS riser (76mm) Boosted / mains cold water pipework (TCWS)
BCWS riser Boosted / mains cold water pipework (TCWS)
22mm BCWS to serve the heating system pressurisation unit Boosted / mains cold water pipework (TCWS)
76mm BCWS to the building Boosted / mains cold water pipework (TCWS)
35mm BCWS to the Cat 5 break tank (BS B.02) Boosted / mains cold water pipework (TCWS)
Cat 5 break tank outlet to BS B.02 pumps Fluid category 5 boosted water (CAT5B)
BS B.02 pump 1 Fluid category 5 boosted water (CAT5B)
BS B.02 pump 2 Fluid category 5 boosted water (CAT5B)
BS B.02 vessel connection Fluid category 5 boosted water (CAT5B)
35mm Cat 5 to pool water specialist plant and wash down points From BS B.02 to Pool plant and wash down Fluid category 5 boosted water (CAT5B)
Isolation valve IV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Three port control valve 3PV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).
Test point TP-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Strainer STR-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Test point TP-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Commissioning set CS-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Single pump P 0.01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).
Drain off cock DOC-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Isolation valve IV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Drain off cock DOC-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Visual pressure gauge PG-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
P
Flexible connection FC-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary return riser (38°C))
Flexible connection FC-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))
Visual pressure gauge PG-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))
P
Automatic air vent AAV-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.
Flow switch FS-A01 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).
F/S
Isolation valve IV-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.01 primary flow riser (45°C))
Isolation valve IV-A04 On ASHP 0.01 flushing bypass Normally closed flushing bypass across the heat pump connections.
Isolation valve IV-A05 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Three port control valve 3PV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).
Test point TP-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Strainer STR-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Test point TP-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Commissioning set CS-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Single pump P 0.02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).
Drain off cock DOC-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Isolation valve IV-A06 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Drain off cock DOC-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Visual pressure gauge PG-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
P
Flexible connection FC-A03 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary return riser (38°C))
Flexible connection FC-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))
Visual pressure gauge PG-A04 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))
P
Automatic air vent AAV-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.
Flow switch FS-A02 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).
F/S
Isolation valve IV-A07 On 160mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.02 primary flow riser (45°C))
Isolation valve IV-A08 On ASHP 0.02 flushing bypass Normally closed flushing bypass across the heat pump connections.
Isolation valve IV-A09 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Three port control valve 3PV-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C)) Motorised three port valve with a bypass from the flow riser. Opens for frost protection and to keep flow through the unit (see sequencer description).
Test point TP-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Strainer STR-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Test point TP-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Commissioning set CS-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Single pump P 0.03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C)) Single head pump on the heat pump return, controlled from the heat pump controls (BMS link shown on the record).
Drain off cock DOC-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Isolation valve IV-A10 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Drain off cock DOC-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Visual pressure gauge PG-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
P
Flexible connection FC-A05 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary return riser (38°C))
Flexible connection FC-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))
Visual pressure gauge PG-A06 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))
P
Automatic air vent AAV-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C)) Automatic air vent at the base of the flow riser, as drawn on the record.
Flow switch FS-A03 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C)) Flow proving device on the heat pump flow, wired to controls (COMMS on the record).
F/S
Isolation valve IV-A11 On 63mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP 0.03 primary flow riser (45°C))
Isolation valve IV-A12 On ASHP 0.03 flushing bypass Normally closed flushing bypass across the heat pump connections.
BMS temperature sensor T-A01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel)) BMS temperature sensor, ASHP common flow.
T
Visual temperature gauge TG-A01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel))
T
Isolation valve IV-A13 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary flow into the thermal store (internal steel))
Isolation valve IV-A14 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel))
Visual temperature gauge TG-A02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel))
T
BMS temperature sensor T-A02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return from the thermal store (internal steel)) BMS temperature sensor, ASHP common return.
T
Isolation valve IV-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow from the thermal store to the dirt separator (45°C))
Isolation valve IV-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow from the thermal store to the dirt separator (45°C))
Isolation valve IV-P03 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C))
BMS temperature sensor T-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C)) BMS temperature sensor, primary flow into the low loss header.
T
Flow switch FS-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C)) Flow device on the primary flow (F on the record, COMMS to BMS).
F/S
Isolation valve IV-P04 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (Primary flow to the low loss header (45°C))
Isolation valve IV-P05 On Dosing pot connection from the primary flow
Isolation valve IV-P06 On Dosing pot connection to the primary return
Isolation valve IV-P07 On Capped off connection on the low loss header (flow side)
Commissioning set CS-P01 On Capped off connection on the low loss header (return side)
Commissioning set CS-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) Sets and measures the primary flow back to the thermal store.
Isolation valve IV-P08 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Test point TP-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Strainer STR-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Test point TP-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Visual pressure gauge PG-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
P
Test point TP-P03 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Twin pump, duty and standby P B.01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) Lowara twin head pump between the low loss header and the thermal store.
Test point TP-P04 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Visual pressure gauge PG-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
P
Isolation valve IV-P09 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Visual temperature gauge TG-P01 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
T
BMS temperature sensor T-P02 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C)) BMS temperature sensor, primary return to the thermal store.
T
Isolation valve IV-P10 On 150mm Primary side LTHW pipework (ASHP primary, 45/38°C) (ASHP primary return, low loss header to thermal store (38°C))
Isolation valve IV-F01 On Pressurisation unit pump 1
Single pump PU 0.01 pump 1 On Pressurisation unit pump 1
Isolation valve IV-F02 On Pressurisation unit pump 1
Isolation valve IV-F03 On Pressurisation unit pump 2
Single pump PU 0.01 pump 2 On Pressurisation unit pump 2
Isolation valve IV-F04 On Pressurisation unit pump 2
BMS temperature sensor T-F01 On Pressurisation unit discharge to the low loss header Pressure device on the pressurisation unit discharge (unlabelled on the record).
T
BMS temperature sensor T-F02 On Pressurisation unit discharge to the low loss header Pressure device on the pressurisation unit discharge (unlabelled on the record).
T
Non return valve NRV-F01 On Pressurisation unit discharge to the low loss header
Isolation valve IV-F05 On Pressurisation unit discharge to the low loss header
Isolation valve IV-F06 On Pressurisation unit discharge to the low loss header
Isolation valve IV-F07 On Tank cold water service to the pressurisation unit tank and quick fill loop
Double check valve DCV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loop
Lockshield valve LSV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loop
Pressure reducing valve PRV-F01 On Tank cold water service to the pressurisation unit tank and quick fill loop
Flexible connection FC-F01 On Tank cold water service to the pressurisation unit tank and quick fill loop Removable quick fill loop from the tank cold water service, with PRV.
Isolation valve IV-F08 On Tank cold water service to the pressurisation unit tank and quick fill loop
Isolation valve IV-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Strainer STR-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Visual pressure gauge PG-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
P
Test point TP-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Twin pump, duty and standby P B.02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Test point TP-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Visual pressure gauge PG-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
P
Isolation valve IV-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
Visual temperature gauge TG-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser)
T
Drain off cock DOC-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature flow, P B.02 to the AHU riser) Flushing valve on the secondary flow.
Commissioning set CS-H01 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)
Visual temperature gauge TG-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)
T
Visual pressure gauge PG-H03 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header)
P
Drain off cock DOC-H02 On 150mm Secondary side LTHW pipework (45/38°C) (AHU constant temperature return to the low loss header) Flushing valve on the circuit return.
Isolation valve IV-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)
Test point TP-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)
Strainer STR-H02 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)
Test point TP-H04 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)
Automatic air vent AAV-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil flow)
Flexible connection FC-H02 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)
Drain off cock DOC-H03 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)
Pressure independent control valve PICV-H01 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return) Controls the AHU R.02 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H05 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)
Isolation valve IV-H04 On 50mm Secondary side LTHW pipework (45/38°C) (AHU R.02 coil return)
Isolation valve IV-H05 On AHU R.02 flushing bypass
Isolation valve IV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)
Test point TP-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)
Strainer STR-H03 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)
Test point TP-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)
Automatic air vent AAV-H02 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H03 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil flow)
Flexible connection FC-H04 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)
Drain off cock DOC-H04 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)
Pressure independent control valve PICV-H02 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return) Controls the AHU R.08 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H08 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)
Isolation valve IV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.08 coil return)
Isolation valve IV-H08 On AHU R.08 flushing bypass
Isolation valve IV-H09 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)
Test point TP-H09 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)
Strainer STR-H04 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)
Test point TP-H10 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)
Automatic air vent AAV-H03 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H05 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil flow)
Flexible connection FC-H06 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)
Drain off cock DOC-H05 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)
Pressure independent control valve PICV-H03 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return) Controls the AHU R.07 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H11 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)
Isolation valve IV-H10 On 65mm Secondary side LTHW pipework (45/38°C) (AHU R.07 coil return)
Isolation valve IV-H11 On AHU R.07 flushing bypass
Isolation valve IV-H12 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)
Test point TP-H12 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)
Strainer STR-H05 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)
Test point TP-H13 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)
Automatic air vent AAV-H04 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H07 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil flow)
Flexible connection FC-H08 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)
Drain off cock DOC-H06 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)
Pressure independent control valve PICV-H04 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return) Controls the AHU R.01 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H14 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)
Isolation valve IV-H13 On 80mm Secondary side LTHW pipework (45/38°C) (AHU R.01 coil return)
Isolation valve IV-H14 On AHU R.01 flushing bypass
Isolation valve IV-H15 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)
Test point TP-H15 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)
Strainer STR-H06 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)
Test point TP-H16 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)
Automatic air vent AAV-H05 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H09 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil flow)
Flexible connection FC-H10 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)
Drain off cock DOC-H07 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)
Pressure independent control valve PICV-H05 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return) Controls the AHU R.04 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H17 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)
Isolation valve IV-H16 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.04 coil return)
Isolation valve IV-H17 On AHU R.04 flushing bypass
Isolation valve IV-H18 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)
Test point TP-H18 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)
Strainer STR-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)
Test point TP-H19 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)
Automatic air vent AAV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H11 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil flow)
Flexible connection FC-H12 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)
Drain off cock DOC-H08 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)
Pressure independent control valve PICV-H06 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return) Controls the AHU R.09 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H20 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)
Isolation valve IV-H19 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.09 coil return)
Isolation valve IV-H20 On AHU R.09 flushing bypass
Isolation valve IV-H21 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)
Test point TP-H21 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)
Strainer STR-H08 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)
Three port control valve 3PV-H01 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow) Motorised three port valve with DRV bypass to the return leg (COMMS to BMS).
Test point TP-H22 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)
Flexible connection FC-H13 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil flow)
Flexible connection FC-H14 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)
Drain off cock DOC-H09 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)
Test point TP-H23 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)
Isolation valve IV-H22 On 25mm Secondary side LTHW pipework (45/38°C) (AHU R.05 coil return)
Isolation valve IV-H23 On AHU R.05 flushing bypass
Double regulating valve DRV-H01 On AHU R.05 three port valve bypass
Isolation valve IV-H24 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)
Test point TP-H24 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)
Strainer STR-H09 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)
Test point TP-H25 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)
Automatic air vent AAV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H15 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil flow)
Flexible connection FC-H16 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)
Drain off cock DOC-H10 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)
Pressure independent control valve PICV-H07 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return) Controls the AHU R.03 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H26 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)
Isolation valve IV-H25 On 32mm Secondary side LTHW pipework (45/38°C) (AHU R.03 coil return)
Isolation valve IV-H26 On AHU R.03 flushing bypass
Isolation valve IV-H27 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)
Test point TP-H27 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)
Strainer STR-H10 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)
Test point TP-H28 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)
Automatic air vent AAV-H08 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow) Automatic air vent with isolating valve at the coil connection.
Flexible connection FC-H17 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil flow)
Flexible connection FC-H18 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)
Drain off cock DOC-H11 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)
Pressure independent control valve PICV-H08 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return) Controls the AHU R.06 heating coil output and limits its flow (COMMS to BMS).
Test point TP-H29 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)
Isolation valve IV-H28 On 20mm Secondary side LTHW pipework (45/38°C) (AHU R.06 coil return)
Isolation valve IV-H29 On AHU R.06 flushing bypass
Isolation valve IV-H30 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)
Test point TP-H30 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)
Pressure independent control valve PICV-H09 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow) Controls the dry change reheat coil (COMMS to BMS). Drawn on the flow leg on the record.
Drain off cock DOC-H12 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)
Flexible connection FC-H19 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil flow)
Flexible connection FC-H20 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Automatic air vent AAV-H09 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Test point TP-H31 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Strainer STR-H11 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Test point TP-H32 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Isolation valve IV-H31 On 25mm Secondary side LTHW pipework (45/38°C) (HB 0.01 dry change reheat coil return)
Isolation valve IV-H32 On HB 0.01 flushing bypass
Isolation valve IV-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Strainer STR-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Visual pressure gauge PG-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
P
Test point TP-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Twin pump, duty and standby P B.03 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Test point TP-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Visual pressure gauge PG-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
P
Isolation valve IV-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
Visual temperature gauge TG-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03)
T
Drain off cock DOC-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger flow, P B.03) Flushing valve on the secondary flow.
Commissioning set CS-L01 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)
Visual temperature gauge TG-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)
T
Visual pressure gauge PG-L03 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header)
P
Drain off cock DOC-L02 On 80mm Secondary side LTHW pipework (45/38°C) (Pool plate heat exchanger return to the low loss header) Flushing valve on the circuit return.
Isolation valve IV-L03 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)
Visual pressure gauge PG-L04 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)
P
Strainer STR-L02 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)
Visual pressure gauge PG-L05 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)
P
Test point TP-L03 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger flow)
Three port control valve 3PV-L01 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger return) Motorised three port valve with DRV bypass from the flow leg (COMMS to BMS).
Isolation valve IV-L04 On 65mm Secondary side LTHW pipework (45/38°C) (160 kW main pool plate heat exchanger return)
Isolation valve IV-L05 On 160 kW main pool plate heat exchanger flushing bypass
Double regulating valve DRV-L01 On 160 kW main pool plate heat exchanger three port valve bypass
Single pump PHE main pool pool pump On 160 kW main pool plate heat exchanger, pool water side (by others)
BMS temperature sensor T-X01 On 160 kW main pool plate heat exchanger, pool water side (by others) Pool water temperature sensor (COMMS).
T
BMS temperature sensor T-X02 On 160 kW main pool plate heat exchanger, pool water side (by others) Pool water high temperature sensor (COMMS).
T
Isolation valve IV-L06 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)
Visual pressure gauge PG-L06 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)
P
Strainer STR-L03 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)
Visual pressure gauge PG-L07 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)
P
Test point TP-L04 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger flow)
Pressure independent control valve PICV-L01 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger return) Controls the learner pool plate heat exchanger (COMMS to BMS).
Isolation valve IV-L07 On 40mm Secondary side LTHW pipework (45/38°C) (40 kW learner pool plate heat exchanger return)
Isolation valve IV-L08 On 40 kW learner pool plate heat exchanger flushing bypass
Single pump PHE learner pool pool pump On 40 kW learner pool plate heat exchanger, pool water side (by others)
BMS temperature sensor T-X03 On 40 kW learner pool plate heat exchanger, pool water side (by others) Pool water temperature sensor (COMMS).
T
BMS temperature sensor T-X04 On 40 kW learner pool plate heat exchanger, pool water side (by others) Pool water high temperature sensor (COMMS).
T
Isolation valve IV-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Strainer STR-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Visual pressure gauge PG-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
P
Test point TP-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Twin pump, duty and standby P B.04 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Test point TP-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Visual pressure gauge PG-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
P
Isolation valve IV-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
Visual temperature gauge TG-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04)
T
Drain off cock DOC-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary flow, P B.04) Flushing valve on the secondary flow.
Commissioning set CS-W01 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)
Visual temperature gauge TG-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)
T
Visual pressure gauge PG-W03 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header)
P
Drain off cock DOC-W02 On 50mm Secondary side LTHW pipework (45/38°C) (Hot water heater primary return to the low loss header) Flushing valve on the circuit return.
Isolation valve IV-W03 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil flow)
Automatic air vent AAV-W01 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil flow)
Drain off cock DOC-W03 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil return)
Isolation valve IV-W04 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.01 primary coil return)
Isolation valve IV-W05 On WH B.01 flushing bypass
Three port control valve 3PV-D01 On WH B.01 hot water outlet Valve on the cylinder hot outlet with a discharge branch through a tundish (T) to low level for drain.
Visual temperature gauge TG-D01 On WH B.01 hot water outlet
T
Isolation valve IV-W06 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil flow)
Automatic air vent AAV-W02 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil flow)
Drain off cock DOC-W04 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil return)
Isolation valve IV-W07 On 40mm Secondary side LTHW pipework (45/38°C) (WH B.02 primary coil return)
Isolation valve IV-W08 On WH B.02 flushing bypass
Three port control valve 3PV-D02 On WH B.02 hot water outlet Valve on the cylinder hot outlet with a discharge branch through a tundish (T) to low level for drain.
Isolation valve IV-D01 On Cold feed to WH B.01 with expansion vessel and relief valve
Safety / expansion relief valve SV-D01 On Cold feed to WH B.01 with expansion vessel and relief valve
Isolation valve IV-D02 On Cold feed to WH B.02 with expansion vessel and relief valve
Safety / expansion relief valve SV-D02 On Cold feed to WH B.02 with expansion vessel and relief valve
Isolation valve IV-D03 On Hot water secondary return via P B.05
Visual temperature gauge TG-D02 On Hot water secondary return via P B.05
T
Strainer STR-D01 On Hot water secondary return via P B.05
Single pump P B.05 On Hot water secondary return via P B.05
Non return valve NRV-D01 On Hot water secondary return via P B.05
Isolation valve IV-D04 On Hot water secondary return via P B.05
Isolation valve IV-D05 On 54mm boosted cold water feed to the hot water heaters via PRV
Strainer STR-D02 On 54mm boosted cold water feed to the hot water heaters via PRV
Pressure reducing valve PRV-D01 On 54mm boosted cold water feed to the hot water heaters via PRV
Non return valve NRV-D02 On 54mm boosted cold water feed to the hot water heaters via PRV
Isolation valve IV-D06 On 54mm boosted cold water feed to the hot water heaters via PRV
Isolation valve IV-C01 On Existing tank cold water down service to BS B.01 suction
Isolation valve IV-C02 On BS B.01 pump 1
Single pump BS B.01 pump 1 On BS B.01 pump 1
Isolation valve IV-C03 On BS B.01 pump 1
Isolation valve IV-C04 On BS B.01 pump 2
Single pump BS B.01 pump 2 On BS B.01 pump 2
Isolation valve IV-C05 On BS B.01 pump 2
Isolation valve IV-C06 On BS B.01 pump 3
Single pump BS B.01 pump 3 On BS B.01 pump 3
Isolation valve IV-C07 On BS B.01 pump 3
Visual temperature gauge TG-C01 On Boosted cold water from BS B.01
T
Visual pressure gauge PG-C01 On Boosted cold water from BS B.01
P
Isolation valve IV-C08 On Boosted cold water from BS B.01
Non return valve NRV-C01 On Boosted cold water from BS B.01
Strainer STR-C01 On Boosted cold water from BS B.01
Pressure reducing valve PRV-C01 On Boosted cold water from BS B.01
Isolation valve IV-C09 On Boosted cold water from BS B.01
Safety / expansion relief valve SV-C01 On Boosted cold water from BS B.01
Isolation valve IV-C10 On Boosted cold water from BS B.01
Visual temperature gauge TG-C02 On Boosted cold water from BS B.01
T
Visual pressure gauge PG-C02 On Boosted cold water from BS B.01
P
Isolation valve IV-C11 On Boosted cold water from BS B.01
Isolation valve IV-C12 On BCWS riser (76mm)
Isolation valve IV-C13 On 22mm BCWS to serve the heating system pressurisation unit
Isolation valve IV-C14 On 35mm BCWS to the Cat 5 break tank (BS B.02)
Isolation valve IV-C15 On 35mm BCWS to the Cat 5 break tank (BS B.02)
Isolation valve IV-K01 On Cat 5 break tank outlet to BS B.02 pumps
Isolation valve IV-K02 On BS B.02 pump 1
Single pump BS B.02 pump 1 On BS B.02 pump 1
Isolation valve IV-K03 On BS B.02 pump 1
Isolation valve IV-K04 On BS B.02 pump 2
Single pump BS B.02 pump 2 On BS B.02 pump 2
Isolation valve IV-K05 On BS B.02 pump 2
Visual temperature gauge TG-K01 On 35mm Cat 5 to pool water specialist plant and wash down points
T
Visual pressure gauge PG-K01 On 35mm Cat 5 to pool water specialist plant and wash down points
P
Isolation valve IV-K06 On 35mm Cat 5 to pool water specialist plant and wash down points
Non return valve NRV-K01 On 35mm Cat 5 to pool water specialist plant and wash down points
Isolation valve IV-K07 On 35mm Cat 5 to pool water specialist plant and wash down points
ASHP 0.01 Packaged air source heat pump c/w integral heat metering and controls sequencer
MCC
ASHP 0.02 Packaged air source heat pump c/w integral heat metering and controls sequencer
MCC
ASHP 0.03 Packaged air source heat pump c/w integral heat metering and controls sequencer
MCC
TS B.01 LTHW thermal store
Dirt/air separator Dirt and air separator on the primary flow
Chemical dosing pot Chemical dosing pot (bypass across primary flow and return)
Low loss header 300mmØ low loss header
PU 0.01 Packaged pressurisation unit and expansion vessel
PU 0.01 vessel 1 Expansion vessel (pressurisation package)
PU 0.01 vessel 2 Expansion vessel (pressurisation package)
AHU R.02 Wet Change Air Handling Unit
AHU
R.02
AHU R.08 Fitness Studio
AHU
R.08
AHU R.07 Sports Hall Air Handling Unit
AHU
R.07
AHU R.01 Pool Air Handling Unit
AHU
R.01
AHU R.04 Dance Studio Air Handling Unit
AHU
R.04
AHU R.09 Squash Court And Viewing
AHU
R.09
AHU R.05 Soft Play Air Handling Unit
AHU
R.05
AHU R.03 Foh & Ancillaries Air Handling Unit
AHU
R.03
AHU R.06 Spin Studio Air Handling Unit
AHU
R.06
HB 0.01 Dry change reheat coil
HB
0.01
PHE main pool 160 kW main pool plate heat exchanger
PHE learner pool 40 kW learner pool plate heat exchanger
WH B.01 Packaged 1000L hot water storage heater c/w 38kW primary heating coil and immersion heaters
WH B.02 Packaged 1000L hot water storage heater c/w 38kW primary heating coil and immersion heaters
EV (WH B.01) Potable expansion vessel, WH B.01 unvented kit
EV (WH B.02) Potable expansion vessel, WH B.02 unvented kit
BS B.01 vessel Booster set expansion vessel (BS B.01)
Water conditioner Water conditioner (scale reducer)
BS B.02 Cat 5 packaged break tank and booster set c/w expansion vessel for pool plant and wash down
BS B.02 vessel Cat 5 booster set expansion vessel (BS B.02)
TCWS
54mmØ HWS
35mmØ HWS R
54mmØ BCWS
DISCHARGE POINT
TO SERVE HEATING SYSTEM PRESSURISATION UNIT
76mmØ BCWS
IV
TP
ST
TP
CS
DC
IV
DC
FC
FC
AAV
F
IV
FB
IV
TP
ST
TP
CS
DC
IV
DC
FC
FC
AAV
F
IV
FB
IV
TP
ST
TP
CS
DC
IV
DC
FC
FC
AAV
F
IV
FB
T
IV
IV
T
IV
IV
IV
T
F
IV
IV
IV
IV
DRV/OP
DRV/OP
IV
TP
STR
TP
TP
TP
IV
T
IV
IV
IV
IV
IV
NRV
IV
IV
IV
DCV
LSV
PRV
IV
IV
STR
TP
TP
IV
CS
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
3PV
TP
FC
FC
TP
IV
FB
DRV
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
STR
TP
AAV
FC
FC
DOC
PICV
TP
IV
FB
IV
TP
PICV
DOC
FC
FC
AAV
TP
STR
TP
IV
FB
IV
STR
TP
TP
IV
CS
IV
STR
TP
3PV
IV
IV
DRV
T
HT
IV
STR
TP
PICV
IV
IV
T
HT
IV
STR
TP
TP
IV
CS
IV
AAV
DOC
IV
FB
IV
AAV
DOC
IV
FB
IV
SV
IV
SV
IV
STR
NRV
IV
IV
STR
PRV
NRV
IV
IV
IV
IV
IV
IV
IV
IV
IV
NRV
ST
PRV
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
IV
NRV
IV
BMS temperature sensor 1 of 4 on the thermal store (COMMS to BMS).
T
BMS temperature sensor 2 of 4 on the thermal store (COMMS to BMS).
T
BMS temperature sensor 3 of 4 on the thermal store (COMMS to BMS).
T
BMS temperature sensor 4 of 4 on the thermal store (COMMS to BMS).
T
BMS temperature sensor on the low loss header (COMMS to BMS).
T
BMS temperature sensor at the base of the low loss header (COMMS to BMS).
T
COMMS
COMMS
COMMS
BMS
BMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
COMMS
13.20 kg/s
160mmØ
1.01 m/s
61 Pa/m
13.20 kg/s
160mmØ
1.01 m/s
61 Pa/m
2.5 kg/s
63mmØ
1.24 m/s
276 Pa/m
26.4 kg/s
180mmØ
1.59 m/s
123 Pa/m
28.9 kg/s
180mmØ
1.74 m/s
146 Pa/m
28.9 kg/s
150mmØ
1.56 m/s
128 Pa/m
27.26 kg/s
150mmØ
1.49 m/s
121 Pa/m
27.26 kg/s
150mmØ
1.49 m/s
121 Pa/m
16.980 kg/s
150mmØ
0.89 m/s
44 Pa/m
17.810 kg/s
150mmØ
0.95 m/s
48 Pa/m
18.261 kg/s
150mmØ
0.99 m/s
51.5 Pa/m
2.109 kg/s
50mmØ
0.96 m/s
191 Pa/m
0.670 kg/s
32mmØ
0.71 m/s
152 Pa/m
14.870 kg/s
100mmØ
1.73 m/s
285 Pa/m
5.416 kg/s
65mmØ
1.47 m/s
311 Pa/m
14.200 kg/s
100mmØ
1.65 m/s
225 Pa/m
7.674 kg/s
80mmØ
1.51 m/s
268 Pa/m
8.784 kg/s
100mmØ
1.06 m/s
90 Pa/m
0.21 kg/s
20mmØ
0.57 m/s
220 Pa/m
1.110 kg/s
40mmØ
0.88 m/s
180 Pa/m
0.530 kg/s
32mmØ
0.61 m/s
97 Pa/m
0.900 kg/s
32mmØ
0.96 m/s
265 Pa/m
0.370 kg/s
25mmØ
0.62 m/s
198 Pa/m
0.650 kg/s
32mmØ
0.73 m/s
141 Pa/m
0.180 kg/s
20mmØ
0.5 m/s
163 Pa/m
0.830 kg/s
32mmØ
0.91 m/s
227 Pa/m
0.451 kg/s
25mmØ
0.74 m/s
290 Pa/m
6.599 kg/s
80mmØ
1.31 m/s
201 Pa/m
5.443 kg/s
65mmØ
1.48 m/s
314 Pa/m
1.157 kg/s
40mmØ
0.85 m/s
200 Pa/m
2.538 kg/s
50mmØ
1.16 m/s
271 Pa/m
1.269 kg/s
40mmØ
0.95 m/s
248 Pa/m
1.269 kg/s
40mmØ
0.95 m/s
248 Pa/m
76mmØ
-
-
BCWS
22mmØ
-
-
BCWS
35mmØ
-
-
BCWS
ASHP PRIMARY FLOW (45'C)
ASHP PRIMARY RETURN (38'C)
MECHANICAL CONTROL
PANEL INTEGRATED TO ASHP
BY MANUFACTURER.
PACKAGED AIR SOURCE HEAT PUMP
c/w INTEGRAL HEAT METERING AND
CONTROLS SEQUENCER
BMS
ASHP PRIMARY FLOW (45'C)
ASHP PRIMARY RETURN (38'C)
MECHANICAL CONTROL
PANEL INTEGRATED TO ASHP
BY MANUFACTURER.
PACKAGED AIR SOURCE HEAT PUMP
c/w INTEGRAL HEAT METERING AND
CONTROLS SEQUENCER
BMS
ASHP PRIMARY FLOW (45'C)
ASHP PRIMARY RETURN (38'C)
MECHANICAL CONTROL
PANEL INTEGRATED TO ASHP
BY MANUFACTURER.
PACKAGED AIR SOURCE HEAT PUMP
c/w INTEGRAL HEAT METERING AND
CONTROLS SEQUENCER
BMS
EXTERNAL BELOW GROUND
PIPEWORK
PREINSULATED MDPE MAINS
INTERNAL PIPEWORK STEEL
TUBE AND FITTINGS
LTHW
THERMAL
STORE
ASHP PRIMARY FLOW (45'C)
DIRT/AIR
SEPERATOR
AAV
DC
CHEMICAL
DOSING POT
IV
DC
300mmØ LOW LOSS HEADER
AAV
DC
300mmØ LOW LOSS HEADER SIZED TO
SUIT SECONDARY SIDE OF THE HEATING
SYSTEM
CAPPED OFF
CONNECTION
CAPPED OFF
CONNECTION
ASHP PRIMARY RETURN (38'C)
TANK
EXPANSION
VESSELS
PACKAGED PRESSURISATION UNIT
AND EXPANSION VESSEL
REMOVABLE
QUICK FILL
LOOP
OVERFLOW
45'C
45'C
45'C
38'C
38'C
38'C
FLUSHING
VALVE
FLUSHING
VALVE
FLUSHING
VALVE
FLUSHING
VALVE
FLUSHING
VALVE
FLUSHING
VALVE
ALL SECONDARY CIRCUITS AT 45'C / 38'C
FLOW AND RETURN WATER
TEMPERATURES
WET CHANGE
AIR HANDLING UNIT
FITNESS STUDIO
SPORTS HALL
AIR HANDLING UNIT
POOL
AIR HANDLING UNIT
DANCE STUDIO
AIR HANDLING UNIT
SQUASH COURT AND
VIEWING
SOFT PLAY
AIR HANDLING UNIT
FOH & ANCILLARIES
AIR HANDLING UNIT
SPIN STUDIO
AIR HANDLING UNIT
DRY CHANGE
REHEAT COIL
FLUSHING
BYPASS
160 kW MAIN POOL
PLATE HEAT
EXCHANGER
(BY OTHERS)
FLUSHING
BYPASS
40 kW LEARNER POOL
PLATE HEAT
EXCHANGER
(BY OTHERS)
T
TO LL FOR
DRAIN
PACKAGED 1000L HOT WATER
STORAGE HEATER c/w 38kW
PRIMARY HEATING COIL AND
IMMERSION HEATERS
T
TO LL FOR
DRAIN
PACKAGED 1000L HOT WATER
STORAGE HEATER c/w 38kW
PRIMARY HEATING COIL AND
IMMERSION HEATERS
EV
EV
CONNECT TO PACKAGE HOT
WATER HEATER
CONNECT TO PACKAGE HOT
WATER HEATER
CONNECT TO PACKAGE HOT
WATER HEATER
CONNECT TO PACKAGE HOT
WATER HEATER
EXISTING TANK
COLD WATER
DOWN SERVICE
BOOSTER SET C/W
EXPANSION VESSEL
BCWS
WATER
CONDITIONER
ACCESS
HATCH
OVERFLOW
HIGH LEVEL ALARM
LOW LEVEL ALARM
DC
CAT 5 PACKAGED BREAK TANK & BOOSTER
SET C/W EXPANSION VESSEL FOR POOL
PLANT AND WASH DOWN
35mmØ CAT 5 TO
POOL WATER
SPECIALIST PLANT &
WASH DOWN POINTS
THE INFORMATION SHOWN ON THIS DRAWING IS DESIGN
INTENT AT THE CURRENT DESIGN STAGE ONLY AND SHALL
BE SUBJECT TO DETAILED DESIGN AND SUPPORTING
CALCULATIONS BY THE MECHANICAL AND ELECTRICAL
SERVICES CONTRACTOR UNDER A DESIGN AND BUILD
APPOINTMENT TO REFLECT ANY DEVELOPMENT AND
PROCURED PLANT. ROUTES AND SIZES SHOWN HAVE BEEN
USED FOR PRELIMINARY COORDINATION PURPOSES ONLY.
ASHP
0.01
P
0.01
ASHP
0.02
P
0.02
ASHP
0.03
P
0.03
TS
B.01
P
B.01
P
B.02
P
B.03
P
B.04
WH
B.01
WH
B.02
P
B.05
BS
B.01
BS
B.02
COPYRIGHT
THIS DRAWING IS COPYRIGHT AND MAY NOT BE ALTERED, REPRODUCED OR USED
OTHER THAN FOR THE CONTRACT WORKS FOR WHICH IT IS ISSUED WITHOUT THE
WRITTEN PERMISSION OF HDN|MEP LTD.
WARNING
DO NOT SCALE OFF THIS DRAWING.
VERIFY ALL DIMENSIONS AND STRUCTURAL DETAILS ON SITE.
IF IN DOUBT, ASK BEFORE ACTING.
RELATED DOCUMENTS
READ THIS DRAWING IN CONJUNCTION WITH THE APPROPRIATE SPECIFICATION(S).
CHECKING
THIS DRAWING HAS BEEN GENERATED USING A COMPUTER AIDED DRAWING SYSTEM, AS
THE SYSTEM GENERATES A NEW DRAWING AT EACH REVISION ONLY THE LATEST
EDITION WILL HAVE BEEN CHECKED.
GENERAL NOTES
1.
THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS,
SPECIFICATIONS AND SCHEDULES.
2.
ALL EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE SLAB /
STRUCTURE AND NOT BE RELIANT ON THE CEILING OR OTHER SERVICES.
3.
ALL PENETRATIONS THROUGH WALL SHALL BE FILLED TO SUIT THE ACOUSTIC
PERFORMANCE AND / OR THE FIRE REQUIREMENTS AS DETAILED ON THE
ARCHITECT'S DRAWINGS.
4.
ALL FINAL CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
HEATING SERVICES NOTES
1.
PRIOR TO INSTALLATION, THE CONTRACTOR SHALL ENSURE FINAL COORDINATION
OF EMITTERS, PIPEWORK AND VALVES WITH THE FINAL FURNITURE LAYOUT.
2.
ALL LOW POINTS TO BE PROVIDED WITH DRAIN COCKS AND HIGH POINTS WITH
AUTOMATIC AIR VENTS.
3.
ALL PIPEWORK TO BE INSULATED AND IDENTIFIED IN ACCORDANCE WITH BS EN
6644:1991. INSULATION WITHIN SWIMMING POOL TO BE ISOGENOPAK FINISH,
ELSEWHERE FOIL FACED FINISH.
4.
ALL FINAL CONNECTIONS SHALL BE 15mmØ FLOW AND RETURN UNLESS STATED
OTHERWISE
5.
SPECIFIC REFERENCE SHALL BE MADE TO THE SCHEMATIC DRAWINGS FOR VALVE
ARRANGEMENTS.
COOLING SERVICES NOTES
1.
REFRIGERANT PIPEWORK SIZES AND SYSTEM REFRIGERANT VOLUME ARE
SPECIALIST DESIGN
2.
ALL PIPEWORK SHALL BE INSULATED AND VAPOUR SEALED THROUGHOUT
PLANTROOM SERVICES LEGEND:
ISOLATION VALVE (IV)
COMMISSIONING SET (DRV / OP)
FLUSHING BY-PASS VALVE (FB)
STRAINER (ST / STR)
2 PORT VALVE
3 PORT VALVE
PRESSURE INDEPENDENT CONTROL VALVE
T
THERMOSTATIC TEMPERATURE SENSOR (BMS)
T
TEMPERATURE GAUGE
P
PRESSURE GAUGE
NON RETURN VALVE
FLEXIBLE CONNECTION
SINGLE HEAD PUMP
TWIN HEAD PUMP
PRIMARY SIDE LTHW PIPEWORK
SECONDARY SIDE LTHW PIPEWORK
BOOSTED / MAINS COLD WATER PIPEWORK
CAT 5 BOOSTED WATER PIPEWORK
DOMESTIC HOT WATER PIPEWORK
POOL WATER SIDE (BY OTHERS)
AF01
AS FITTED
28.04.26
MPO
DB
P01
PRELIMINARY ISSUE
xx.04.25
MW
DB
REV
DESCRIPTION
DATE
DRAWN
CHECK
STATUS
AS FITTED
CLIENT
WESTGATE LEISURE SERVICES
PROJECT
ELMWOOD LEISURE CENTRE
DRAWING TITLE
MECHANICAL SERVICES
PRIMARY PLANT ROOM SCHEMATIC
SCALE @ A0
N.T.S
DRAWN BY
MW
1ST ISSUE DATE
JUN '24
CHECKED BY
DB
COMPANY ADDRESS
Roall Hall, Roall Lane,
Eggborough, North Yorkshire,
DN14 0NY
DRAWINGS PRODUCED BY
Hensall Mechanical Services Ltd. www.hensall.com
Tel 01977 661318 Fax 01977 662127
PROJECT ADDRESS
Elmwood Leisure Centre
Market Gate Road, Elmwood EL6 4QT
JOB No.
HEN0203
DRG No.
HEN0203-HEN-00-ZZ-DR-M-5991
REV.
AF01
ASITE DOC REF.
HEN0203-HEN-00-ZZ-DR-M-5991
INTERACTIVE REPLICA
Redrawn by SF, 15.10.26, from AF01. No design change.
+
−